Section 903.2.7 of the IFC is amended to read:

An automatic sprinkler system shall be provided throughout buildings containing a Group B or M occupancy where one of the following conditions exists:

(1) The fire area exceeds 10,000 square feet (929 m2).

(2) A fire area is located more than three stories above grade plane.

(3) The combined areas of all fire areas on all floors, including any mezzanines, exceeds 20,000 square feet (1,858 m2).

(4) Group M occupancies used for the display and sale of upholstered furniture or mattresses exceeds 5,000 square feet (464 m2).

(Added by Amended Ord. 21-031, July 14, 2021, Eff date July 25, 2021).