30.53A.903.2.9 Group S-1.
This section is included in your selections.
Section 903.2.9 of the IFC is amended to read:
An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists:
(1) A Group S-1 fire area exceeds 10,000 square feet (929 m2).
(2) A Group S-1 fire area is located more than three stories above grade plane.
(3) The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 20,000 square feet (1,858 m2).
(4) A Group S-1 fire area used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m2).
(Added by Amended Ord. 21-031, July 14, 2021, Eff date July 25, 2021).