Section 903.2.4 of the IFC is amended to read:

An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exists:

(1) A Group F-1 fire area exceeds 10,000 square feet (929 m2).

(2) A Group F-1 fire area is located more than three stories above grade plane.

(3) The combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 20,000 square feet (1,858 m2).

(4) A Group F-1 occupancy used for the manufacture of upholstered furniture or mattresses exceeds 2,500 square feet (232 m2).

(Added by Amended Ord. 21-031, July 14, 2021, Eff date July 25, 2021).