Section 903.2.3 of the IFC is amended to read:

An automatic sprinkler system shall be provided for fire areas containing Group E occupancies where the fire area has an occupant load of 51 or more, calculated in accordance with Table 1004.1.2.

EXCEPTIONS:

(1) Portable school classrooms with an occupant load of 50 or less calculated in accordance with Table 1004.1.2, provided that the aggregate area of any cluster of portable classrooms does not exceed 5,000 square feet (465 m2); and clusters of portable school classrooms shall be separated as required by the building code; or

(2) Portable school classrooms with an occupant load from 51 through 98, calculated in accordance with Table 1004.1.2, and provided with two means of direct independent exterior egress from each classroom in accordance with Chapter 10, and one exit from each class room shall be accessible, provided that the aggregate area of any cluster of portable classrooms does not exceed 5,000 square feet (465 m2); and clusters of portable school classrooms shall be separated as required by the building code; or

(3) Fire areas containing day care and preschool facilities with a total occupant load of 100 or less located at the level of exit discharge where every room in which care is provided has not fewer than one exit discharge door.

(Added by Amended Ord. 21-031, July 14, 2021, Eff date July 25, 2021).