30.53A.903.2.1.4 Group A-4.
This section is included in your selections.
Section 903.2.1.4 of the IFC is amended to read:
An automatic sprinkler system shall be provided throughout stories containing Group A-4 occupancies and throughout all stories from the Group A-4 occupancy to and including the levels of exit discharge serving the occupancy where one of the following conditions exists:
(1) The fire area exceeds 10,000 square feet (929 m2).
(2) The fire area has an occupant load of 300 or more.
(3) The fire area is located on a floor other than a level of exit discharge serving such occupancies.
(Added by Amended Ord. 21-031, July 14, 2021, Eff date July 25, 2021).