Section 903.2.1.1 of the IFC is amended to read:

An automatic sprinkler system shall be provided throughout stories containing Group A-1 occupancies and throughout all stories from the Group A-1 occupancy to and including the level of exit discharge serving that occupancy where one of the following conditions exists:

(1) The fire area exceeds 10,000 square feet (929 m2).

(2) The fire area has an occupant load of 300 or more.

(3) The fire area is located on a floor other than a level of exit discharge serving such occupancies.

(4) The fire area contains a multi-theater complex.

(Added by Amended Ord. 21-031, July 14, 2021, Eff date July 25, 2021).